Euclid E3-Flowable is a three-component, high-flow, high-strength, expansive epoxy grout for large plates and narrow configurations where flow is critical. DL Technology aggregate cuts mixing dust.
Euclid E3-Flowable is a three-component, high-flow, high-strength epoxy grout for precision support of large plates, rails, and machinery where the grout has to run into narrow clearances. Patented DL Technology aggregate cuts the dust released while mixing and handling. The grout is expansive, so it develops positive bearing under generators, compressors, motors, pumps, and inverted baseplates.
| Property | Value |
|---|---|
| Manufacturer | Euclid Chemical |
| Product | E3-Flowable |
| Type | High-flow epoxy grout with DL Technology aggregate |
| Yield | 1.53 ft³ standard kit (5 aggregate bags) |
| Working time | 95 minutes at 73°F |
| Thickness per lift | 1/2 to 6 in |
| Effective bearing area | > 95% |
| Compressive strength | 10,000 psi at 1 day; 12,500 psi at 28 days |
| Bond strength | 3,500 psi at 28 days |
| Flexural strength | 4,300 psi at 28 days |
| Packaging | 1.53 ft³ kit |
| Shelf life | 2 years unopened |
Product documents: E3-Flowable Technical Data Sheet
When should I use Euclid E3-Flowable?
Use Euclid E3-Flowable for large or wide plates that need precision grouting, and for narrow gaps including rails, keyways, inverted baseplates, and anchor bolts, where high flow is critical.
Why is mixing Euclid E3-Flowable less dusty than a typical epoxy grout?
Euclid’s patented DL Technology aggregate is formulated to greatly reduce the dust released during mixing and handling of Euclid E3-Flowable.
What effective bearing area does Euclid E3-Flowable achieve against a baseplate?
Euclid rates Euclid E3-Flowable at greater than 95% effective bearing area, meaning the grout contacts the plate instead of leaving voids.
How thick can Euclid E3-Flowable be placed in one lift?
Euclid publishes a 1/2 in minimum and 6 in maximum per lift for Euclid E3-Flowable in a large mass.
When do I pick Euclid E3-Flowable instead of Euclid E3-Deep Pour?
Use Euclid E3-Flowable when high flow under large plates and tight clearances matters, 1/2 to 6 in per lift. Use Euclid E3-Deep Pour for mass placements Euclid rates up to 18 in per lift.
What early strength does Euclid E3-Flowable reach?
Euclid publishes 10,000 psi compressive at 1 day at 73°F on the standard unit, and 12,500 psi at 28 days.